National High Level Isolation Unit, Mater Misericordiae University Hospital
Back to Projects

Our Role

Project Type

Project Value
Features:
Winner – ACEI Design Excellence Awards 2026
National High Level Isolation Units (NHLIU), or Biocontainment Units (BCUs) in the USA, are required to safely manage and effectively treat patients with High Consequence Infectious Diseases (HCID). There are less than twenty National High Level Isolation Units in the world, and the new National Isolation Unit (NIU) at the Mater Misericordiae University Hospital now serves as one of those few.
The design of the National Isolation Unit has many complex Mechanical and Electrical Services and Design requirements, in compliance with the NHS suite of documents, HTM/HBNs, etc. The two-bed facility has been designed to operate as a “hospital within a hospital”, and can operate irrespective of whatever else is happening within the hospital. It comprises of two patient suites (patient rooms with en-suite and ancillary services rooms such as donning, doffing rooms, etc.) overseen by a large Staff Base located between the two suites to give full visibility to the patient rooms via floor-to-ceiling glazed walls. A dedicated CAT 3 lab, pharmacy, and plant rooms within the unit provide support. Each patient suite has dedicated Mechanical & Electrical Systems, allowing it to operate independent of the other.
JV Tierney provided the full Mechanical, Electrical, and Sustainable Design Services for this development. This includes:
- Air systems and air pressure profiling were carefully designed to ensure cascading pressure regimes are maintained in order to protect staff as they move between various support and patient rooms and to ensure airborne pathogens are not transmitted outside of the infected patient suite.
- Extract Ventilation comprising of HEPA filtered grilles, welded plastic ductwork with N+1 redundancy safe change HEPA filtration, and N+1 redundancy extract fans on each patient suite extract ventilation system.
- Customised decontamination showers carefully designed to chemically decontaminate, wash, and dry staff in their full PPE clothing to prevent bacterial transfer.
- Independent autoclaves installed in red and yellow doffing rooms to minimise and prevent contamination.
- Electricity supply backed up by N+1 redundant generators and with N+1 redundant tertiary power via Uninterruptable Power Supply (UPS) and Medical Isolation Power Supply (IPS) systems.
- Mechanical plant backed up by N+1 redundant UPS systems.
- All lighting in patient suites and staff bases are powered via N+1 redundant static invertors.
- All plant in the patient suites designed to withstand gaseous fumigation.
- Mechanical and Electrical systems designed and coordinated to ensure all systems serving the patient suites can be maintainable and accessible without entering the patient suite in order to protect maintenance staff.
- Dual diverse fibre backbone cabling for ICT network resilience.
- Door interlocking facilities to prevent cross-contamination and ensure correct movement through the potentially contaminated zones.